3000V isolation on CAN side
The CAN port of i-7530 has 3000V isolation. This isolation can protect the local
RS-232 devices from the damaging signals coming from the CAN network.
Watchdog inside
The i-7530 Watchdog has a hardware reset circuit to monitor the i-7530’s
operation status. When working in harsh or noisy environments, the i-7530 may be
affected by the external signal. The circuit will help the i-7530 to continue
operating.
Power and Error indicator display
There are two indicators on the i-7530.The power indicator can help user to
check whether the i-7530 is in standby or is transmitting/receiving messages.
The Error indicator will be turned on when some errors occur on the i-7530.
Microprocessor inside with 20MHz
CAN interface connector: D-Sub 9-pin
82C250 CAN transceiver
Built-in CAN/RS-232 Converter firmware
Max transmission speed up to 1M bps for CAN and 115.2K bps for RS-232
Software configurable CAN and RS-232 communication parameters
Max transmission distance over 1000m (follow CAN specification)
Support both CAN 2.0A and CAN 2.0B
Build-in jumper to select 120 ohm terminal resistor
Mount easily on DIN-rail
Power, data flow and error indicator for CAN and RS-232
Watchdog inside
Support transparent communication mode
Provide a group of RS-232 devices a method to be the network system
(full-duplex communication mode of RS-232 devices is not supported)
CAN bus Baud rate configuration
CAN acceptance filter configuration
CAN 2.0A or 2.0B specific selection
RS-232 Baud rate and data bit setting
RS-232 responded selection
Easy test to transmit/receive CAN messages
Setting for I-7530 communication mode (normal mode or pair connection mode) |