7011-M Modbus Master to Datascan Interface module
The Datascan 7011-M Modbus™ Gateway module allows the Datascan 7000 network to be connected to a host computer running SCADA Packages using the Modbus ASCII Master Protocol (7 or 8 bit support). This provides the ability for the Modbus Package to configure, read and write to Datascan Channels.
- Connects SCADA packages running Modbus? ASCII Master Protocol to the Datascan 7000 Network
- Upto 38k4 Baud Data Transfer
- 500V Isolation from Network
- Compact DIN-Rail Mounting
- RS485 Network
Transmission Rate : 93.75kBaud
Data Rate : 1000 results/sec
Total Channels/network : 1000
Max. No. of nodes (processors) : 32
Max. Network Length : 1.2 km (4000 ft)
Isolation : 500Vdc - RS232 Port
Baud Rates : 4800, 9600, 19k2, 38k4
Isolation : 500Vdc
Max Distance (direct) : 10m to host - Recommended Network Cable
Belden 9207 : upto 1.2km
Belden 8761 : upto 300m - Power Requirements:
24V AC or DC @ 500mA
Battery Backup life : 5 Years (unpowered) - Dimensions : 230 W x 80 D x 123 H (mm)
Weight : 600g - Environmental:
Operating Temp.Range : -10 to +60 °C
Storage Temp. Range : -20 to +80 °C
Relative Humidity : 90% non-condensing
- 7011-M Datasheet [7011Mbroc.pdf]
- Datascan Brochure [DS7000bro.pdf]
- Datascan User Guide [DSCANUSR.pdf]