I-7011P Thermocouple I/P Module (1AI + 1DI +2DO) £109.00

This Thermocouple Input module is ideal where only a single temperature (or voltage or current) needs to be monitored.

It also has an integral Digital Input channel to accept an input from a switch/relay or similar, along with 2 Digital Outputs which are useful for Alarm Output.

Quantity:     

Features

  • 16 bit ADC
  • 3000V dc inter module isolation
  • Integrated digital input and output
  • Event counters
  • Autonomous alarm output
  • Direct measurement of thermocouples, voltage and current
  • Cold Junction Compensation for thermocouples
  • Can be Configured using simple ASCII Commands
  • Specifications

    Analog Input
    • Resolution: 16 bits
    • No of inputs: 1 differential
    • Input Type: DC voltage, 0-20mA, T/couple
    • Sampling Rate: 10 Hz
    • Input Ranges: +/-15mV, +/-50mV, +/-100mV, +/-500mV, +/-1V, +/-2.5V, +/-20mA (with optional 125R resistor)
    • Thermocouple ranges
      J= -210ºC to +760ºC
      K= -270ºC to +1372ºC
      T= -270ºC to +400ºC
      E= -270ºC to +1000ºC
      R= 0ºC to +1768ºC
      S= 0ºC to +1768ºC
      B= 0ºC to +1820ºC
      N= -270ºC to +1300ºC
      C= 0ºC to +2320ºC
      L = -200ºC to +800ºC
      M = -200ºC to +100ºC
    • Accuracy = 0.05%
    • Common Mode Rejection = 150dB
    • Input Impedance = 20M Ohms
    Digital Input
    • Channels = 1
    • Logic 0 = +1V max
    • Logic 1 = +3.5V to +30V
    • Max. Input Frequency = 50Hz
    • Min. Pulse Width = 1ms

    Digital Output

    • Channels = 2
    • Output Type = Sink, Open collector to 30V
    • Output Load = 30mA max. per channel
    • Power Dissipation = 300mW

    Other

    • Interface = RS485
    • Format : N,8,1
    • Baud Rate : 1200 - 115200 bps
    • LED Display = Power/Comms indicator
    • Power Input = +10V to +30V dc
    • Power Consumption = 0.9W
    • Operating Temp. = -25 to +75ºC
    • Storage Temp. = -40 to +85ºC
    • Humidity = 5 to 95%, non-condensing